Customization: | Available |
---|---|
Application: | Power |
Phase: | Three |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Model | SFZ11-125000/220 | ||
Standard | IEC60076 | ||
Rated Voltage(kV) | 230±6x2.5%/36 | ||
Rated Power(HV/LV)(KVA) |
100000/125000 | ||
Rated current(HV/LV)(A) |
314A / 2005A | ||
Tapping | Off-load | ||
Tapping range | ±2x2.5% | ||
Rated Frequency | 50Hz | ||
Cooling Method | ONAN/ONAF | ||
No-load losses | 85kW Tolerance according to IEC |
||
Load losses | 340kW Tolerance according to IEC |
||
Vector Group | YNd11 | ||
Insulation grade | A | ||
Sound level | 70dB(A) Sound pressure level |
||
Impedance | |||
HV-LV | 12.5@125MVA | ||
Insulation level | |||
HV winding | Basic Lighting impulse | Line:1050kV Neutral: 650kV |
|
Power frequency withstand voltage | Line:460kV Neutral: 275kV |
||
LV winding |
Basic Lighting impulse | 170kV | |
Power frequency withstand voltage | 70kV | ||
Temperature rise | |||
Winding Average K | 57 | ||
Top oil K | 52 |