6~10.5kv 2500kVA 20kv 3150kVA Oil-Immersed Distribution Transformer

Product Details
Customization: Available
Application: Power
Phase: Three
Diamond Member Since 2020

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Importers and Exporters
The supplier has import and export rights
High Repeat Buyers Choice
More than 50% of buyers repeatedly choose the supplier
Years of Export Experience
The export experience of the supplier is more than 10 years
Experienced Team
The supplier has 12 foreign trading staff(s) and 9 staff(s) with over 6 years of overseas trading experience
to see all verified strength labels (30)
  • 6~10.5kv 2500kVA 20kv 3150kVA Oil-Immersed Distribution Transformer
  • 6~10.5kv 2500kVA 20kv 3150kVA Oil-Immersed Distribution Transformer
  • 6~10.5kv 2500kVA 20kv 3150kVA Oil-Immersed Distribution Transformer
  • 6~10.5kv 2500kVA 20kv 3150kVA Oil-Immersed Distribution Transformer
  • 6~10.5kv 2500kVA 20kv 3150kVA Oil-Immersed Distribution Transformer
  • 6~10.5kv 2500kVA 20kv 3150kVA Oil-Immersed Distribution Transformer
Find Similar Products

Basic Info.

Model NO.
S11~S22
Cooling Method
Oil-immersed Type Transformer
Winding Type
Multi-winding Transformer
Certification
ISO9001-2000, ISO9001
Usage
Distribution Transformer
Frequency Characteristics
Power Frequency
Shape of Core
Ring
Brand
Ceeg
Rated Capacity
30~3150kVA
Primary Voltage
6/6.3/6.6/10/10.5/11kv/20kv
Secondary Voltage
0.4kv
Frequency
50/60Hz
Impedance
4%/4.5%
Connection Symbol
Dyn11/Yyn0
Tapping Range
±2*2.5%/±5%
Short Circut Loss
4~6
Transport Package
International Wooden Case or According to Client′s
Trademark
CEEG
Origin
Jiangsu, China
HS Code
8504349000
Production Capacity
20

Product Description

Brief Introduction

This series of products feature low loss, low noisy, low temperature rising, low partial discharge and high reliability, as well as core-hoisting free and no leakage. With the approval of the National Transformer Quality Inspection and Testing Center, all the index of the transformer achieve or above the GB/T3837-2003 national standard.



Model

S  F  Z  10-×××/××

S/N Symbol Meaning
1 S Three phases
2 F Air-cooling(blank for Natural cooling)
3 Z On-load tap changing(bland for no-load tap changing)
4 10 Symbol of Performance level
5 xxx Rated capacity,kVA
6 xx Voltage grade of HV winding,kV



Features 

1.    Scientific and advanced design scheme

By using computer software to analyze the winding electric field under high voltage, it can calculate the exact distribution of winding electric field grads and then to make sure the winding structure can meet the impulse under high voltage. Analyzing and calculating the insulation structure of the transformer and using the scientific insulation structure to ensure the products operate safely. Analyzing and calculating the magnetic leakage and temperature field to ensure the field performance in accordance to the design demand. Optimizing the lamination design to minimize the magnetic distortion in the gap and to enhance the no-load performance.

2.    Iron Cores

The iron core adopts high quality grain-oriented cold-rolled silicon-steel sheet and is cut by a special shearing machine which result in just a tiny burr. The application of multi-steps and 45°all-leaning joints lowers the no-load loss,  no-load current, and noise efficiently. The core clamping device adopts a board structure which result in high mechanical intensity. Fasten nails can ensure enough transformer axis padding block pressure.

3.    High purity oxygen free cooper windings, reduce the load loss

The inner coil was wound directly on the insulation barrel, where chamfering spacers and padding blocks were applied to uniform the electric field and enhance stability. And, BDK-80M synchronized lifting-up equipment was applied in assembly to ensure the axial location of the windings and reinforce the axial strength.

4. Tank

Wide-width steel plate is adopted to reduce welding seams on the flat roof, folded plate type tank, it has a concise and dedicate appearance and also high mechanical strength which passed the standard positive pressure and vacuum test. In addition, special welding technology and groove type flange ensure the tank and the pipes are able of long time use without leakage. Wide plate radiation systems equipped with heavy-duty and low noise blowers raise up the heat dissipating center, improve efficiency, reduce radiating plates, and prevent leakage. It can be directly mounted on the transformer. And capsule type conservator can effectively delay the aging of the oil what is implanted in under vacuum condition to reinforce the electric strength.

5. Protection System

Pt100 thermal resistors temperature control system is generally applied in the transformer body, a pressure relief valve with contacts is equipped on the top of tank, an oil indicator with contact and vacuum relays are equipped on the conservator, and as well, the oil pressure indicator with contacts is equipped in the tank. All this equipment can be applied for signal conversion and transfer. Both HV and LV bushings are pollution-retardant porcelain oil types, which can lengthen the insulation space and be applied in high pollution conditions. Padding plates and terminal case are made of stainless steel to make an elegant appearance.


Technical Parameters
 

Performance Data of the S11-M-30~3150/10 Distribution Transformer

Rated Capacity HV Tapping Range LV Vector Group No Load Loss (kW) Load Loss (kW) (75ºC) No Load Current (%) Short-circuit Impedance
30 6
6.3
10
10.5
±5
±2x2.5%
0.4 Dyn11
Yyn0
0.1 0.63 1.50





4.0
50 0.13 0.91 1.30
63 0.15 1.09 1.20
80 0.18 1.31 1.20
100 0.20 1.58 1.10
125 0.24 1.89 1.10
160 0.28 2.31 1.00
200 0.34 2.73 1.00
250 0.40 3.20 0.90
315 0.48 3.83 0.90
400 0.57 4.52 0.80
500 0.68 5.41 0.80
630 0.81 6.20 0.60

4.5
800 0.98 7.50 0.60
1000 1.15 10.30 0.60
1250 1.36 12.00 0.50
1600 1.64 14.50 0.50
2000 1.94 18.30 0.40
5.0
2500 2.29 21.20 0.40
3150 2.81 26.66 0.40



Performance Data of the S11-M-30~3150/20 Distribution Transformer

Rated Capacity HV Tapping Range LV Vector Group No Load Loss (kW) Load Loss (kW) (75ºC) No Load Current (%) Short-circuit Impedance
30







20








±5
±2x2.5%








0.4








Dyn11
Yyn0
0.10 0.69 2.1





5.5
50 0.13 1.01 2.0
63 0.15 1.20 1.9
80 0.18 1.44 1.8
100 0.20 1.73 1.6
125 0.24 2.08 1.5
160 0.29 2.54 1.4
200 0.34 3.00 1.3
250 0.40 3.52 1.2
315 0.48 4.21 1.1
400 0.57 4.97 1.0
500 0.68 5.94 1.0
630 0.81 6.82 0.9

6
800 0.98 8.52 0.8
1000 1.15 11.33 0.7
1250 1.38 13.20 0.7
1600 1.66 15.95 0.6
2000 1.95 19.14 0.6
2500 2.34 22.22 0.5
3150 2.78 26.42 0.5



Performance Data of the S13-M-30~2500/10 Distribution Transformer

Rated Capacity HV Tapping Range LV Vector Group No Load Loss (W) Load Loss (kW) (75ºC) No Load Current (%) Short-circuit Impedance
30






6
6.3
10
10.5








±5
±2x2.5%









0.4








Dyn11
Yyn0
80 630/600 1.5





4.0
50 100 910/870 1.3
63 110 1090/1040 1.2
80 130 1310/1250 1.2
100 150 1580/1500 1.1
125 170 1890/1800 1.1
160 200 2310/2200 1.0
200 240 2730/2600 1.0
250 290 3200/3050 0.9
315 340 3830/3650 0.9
400 410 4520/4300 0.8
500 480 5410/5150 0.8
630 570 6200 0.6

4.5
800 700 7500 0.6
1000 830 10300 0.6
1250 970 12000 0.5
1600 1170 14500 0.5
2000 1360 18300 0.4 5.0
2500 1600 21200 0.4



Performance Data of the S20-M-30~2500/10 Distribution Transformer

Rated Capacity HV Tapping Range LV Vector Group No Load Loss (W) Load Loss (kW) (75ºC) No Load Current (%) Short-circuit Impedance
30






6
6.3
10
10.5








±5
±2x2.5%









0.4








Dyn11
Yyn0
70 505/480 1.5





4.0
50 90 730/695 1.3
63 100 870/830 1.2
80 115 1050/1000 1.2
100 135 1265/1200 1.1
125 150 1510/1440 1.1
160 180 1850/1760 1.0
200 215 2185/2080 1.0
250 260 2560/2440 0.9
315 305 3065/2920 0.9
400 370 3615/3440 0.8
500 430 4330/4120 0.8
630 510 4960 0.6

4.5
800 630 6000 0.6
1000 745 8240 0.6
1250 870 9600 0.5
1600 1050 11600 0.5
2000 1225 14640 0.4 5.0
2500 1440 14840 0.4


Performance Data of the S22-M-30~2500/10 Distribution Transformer

Rated Capacity HV Tapping Range LV Vector Group No Load Loss (W) Load Loss (kW) (75ºC) No Load Current (%) Short-circuit Impedance
30






6
6.3
10
10.5








±5
±2x2.5%









0.4








Dyn11
Yyn0
65 455/430 1.5





4.0
50 80 655/625 1.3
63 90 785/745 1.2
80 105 945/900 1.2
100 120 1140/1080 1.1
125 135 1360/1295 1.1
160 160 1665/1585 1.0
200 190 1970/1870 1.0
250 230 2300/2195 0.9
315 270 2760/2630 0.9
400 330 3250/3095 0.8
500 385 3900/3710 0.8
630 460 4460 0.6

4.5
800 560 5400 0.6
1000 665 7415 0.6
1250 780 8640 0.5
1600 940 10440 0.5
2000 1085 13180 0.4 5.0
2500 1280 13360 0.4

6~10.5kv 2500kVA 20kv 3150kVA Oil-Immersed Distribution Transformer
6~10.5kv 2500kVA 20kv 3150kVA Oil-Immersed Distribution Transformer

6~10.5kv 2500kVA 20kv 3150kVA Oil-Immersed Distribution Transformer
6~10.5kv 2500kVA 20kv 3150kVA Oil-Immersed Distribution Transformer
6~10.5kv 2500kVA 20kv 3150kVA Oil-Immersed Distribution Transformer
6~10.5kv 2500kVA 20kv 3150kVA Oil-Immersed Distribution Transformer

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now