Cast Resin Transformer Designed for 6.3kv Primary Voltage Use

Product Details
Customization: Available
Application: Power
Phase: Three
Diamond Member Since 2020

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

High Repeat Buyers Choice
More than 50% of buyers repeatedly choose the supplier
Years of Export Experience
The export experience of the supplier is more than 10 years
Experienced Team
The supplier has 12 foreign trading staff(s) and 9 staff(s) with over 6 years of overseas trading experience
Patents Awarded
The supplier had awarded 2 patents, you can check the Audit Report for more information
to see all verified strength labels (30)
  • Cast Resin Transformer Designed for 6.3kv Primary Voltage Use
  • Cast Resin Transformer Designed for 6.3kv Primary Voltage Use
  • Cast Resin Transformer Designed for 6.3kv Primary Voltage Use
  • Cast Resin Transformer Designed for 6.3kv Primary Voltage Use
  • Cast Resin Transformer Designed for 6.3kv Primary Voltage Use
  • Cast Resin Transformer Designed for 6.3kv Primary Voltage Use
Find Similar Products

Basic Info.

Model NO.
SC(B)
Cooling Method
Dry-type Transformer
Winding Type
Multi-winding Transformer
Certification
ISO9001-2000, ISO9001, CE, ISO14001, ISO45001, ISO50001
Usage
Distribution Transformer
Frequency Characteristics
Power Frequency
Shape of Core
Ring
Brand
Ceeg
Rated Capacity
100-25000kVA
Primary Voltage
6/6.3/6.6/10/10.5/11/20/35kv
Secondary Voltage
11/10.5/6.3/6/3.15/0.4kv
Insulation Level
C, H, F
Frequency
50/60Hz
Impedance
4%/6%
Connection Symbol
Dyn11/Yyn0
Tapping Range
±2*2.5%/±5%
Standard
IEC60076
Core Material
Silicon Steel
Cooling Way
an/Af
Working Temperature
-20ºC~60ºC
Transport Package
International Wooden Case or According to Client′s
Trademark
CEEG
Origin
Jiangsu, China
HS Code
8504349000
Production Capacity
10000 Pieces/Year

Product Description

China Electric Equipment (Jiangsu) Transformer Manufacture Co., Ltd. proudly stands as the pioneering company in China to achieve the prestigious KEMA E2, C2, F1 certifications for our cast resin transformers, earning us recognition for quality and innovation.

CEEG's innovative cast resin dry-type transformers are patented marvels of technology. They are exquisitely crafted for indoor environments where fire and explosion safety are paramount, as well as high-temperature and moisture conditions often found in commercial centers, residential complexes, hospitals, and manufacturing facilities. These vacuum cast coil transformers are meticulously engineered to meet stringent outdoor requirements, including those in petrochemical operations. Their remarkable adaptability to seasonal load fluctuations and overload scenarios makes them the top choice for encapsulated distribution transformers, ensuring safety and reliability.

Working Environment
Precision engineered for a temperature range of -20ºC to 60ºC, ensuring optimal performance.

Insulation

Material

expoxy resin class H / class C Nomex paper

Structure

 

HV coil is multi layer sectional cylinder structure, LV coil is foil with longitudinal air chamber structure.

Reliability

Insulation class

H(180ºC)

Tem. rise of coil

125K(normal 100K)

Over-load capacity

continuously 120%

Cooling method

AN/AF

 Environmental Protection

Noise

Low

Recycling

easy recycling and low pollution



Product Features

1. Exceptionally reliable with minimal energy loss, maintaining low partial discharge levels (below 5PC), low noise output, and superior heat dissipation capabilities, capable of handling up to 150% overload in forced air cooling settings.

2. Unmatched moisture resistance, able to operate flawlessly in environments with up to 100% humidity.

3. Ensures safe, fire-proof, and eco-friendly operations, perfect for direct installation in load-rich environments.

4. Outfitted with an advanced temperature protection and control system for seamless performance.

5. Designed for hassle-free maintenance, straightforward installation, and cost-efficient operation throughout its lifespan.



Export Case
Since 2014, we have been proudly supplying the CEEG SCB and SC series of cast resin dry-type transformers to LafargeHolcim. These transformers have been seamlessly integrated and are performing exceptionally well in LafargeHolcim's cement plants across Nigeria, the Philippines, and Cameroon, showcasing our commitment to global excellence.


Cast Resin Transformer Designed for 6.3kv Primary Voltage Use
Cast Resin Transformer Designed for 6.3kv Primary Voltage Use
 

Class F Insulation SCB10-315~2500/10

Rated High Voltage:10(10.5,11,6.6,6.3,6)kV

Rated Low Voltage:0.4kV

Vector Group: Dyn11or Yyn0

Insulation Level: Ll 75 AC 35 / Ll AC 3; Tap Range:±2*2.5%

Model

UK%

P0(W)

Pk(120ºC)(W)

I0%

LPA(AN)dB

Gauge m x n (mm)

SCB10-315/10

4

880

3470

1.0

55

660 x 660

SCB10-400/10

4

980

3990

1.0

55

660 x 660

SCB10-500/10

4

1160

4880

1.0

57

660 x 660

SCB10-630/10

4

1340

5880

0.85

57

820 x 820

SCB10-630/10

6

1300

5960

0.85

57

820 x 820

SCB10-800/10

6

1520

6960

0.85

58

820 x 820

SCB10-1000/10

6

1770

8130

0.85

58

820 x 820

SCB10-1250/10

6

2090

9690

0.85

60

820 x 820

SCB10-1600/10

6

2450

11700

0.85

60

820 x 820

SCB10-2000/10

6

3050

14400

0.70

62

820 x 820

SCB10-2500/10

6

3600

17100

0.70

62

820 x 820

 

Class F Insulation SCB11-315~2500/10

Rated High Voltage:10(10.5,11,6.6,6.3,6)kV

Rated Low Voltage:0.4kV

Vector Group: Dyn11or Yyn0

Insulation Level: Ll 75 AC 35 / Ll AC 3; Tap Range:±2*2.5%

Model

UK%

P0(W)

Pk(120ºC)(W)

I0%

LPA(AN)dB

Gauge m x n (mm)

SCB11-315/10

4

790

3470

1.0

55

660 x 660

SCB11-400/10

4

880

3990

1.0

55

660 x 660

SCB11-500/10

4

1040

4880

1.0

57

660 x 660

SCB11-630/10

4

1200

5880

0.85

57

820 x 820

SCB11-630/10

6

1170

5960

0.85

57

820 x 820

SCB11-800/10

6

1360

6960

0.85

58

820 x 820

SCB11-1000/10

6

1590

8130

0.85

58

820 x 820

SCB11-1250/10

6

1880

9690

0.85

60

820 x 820

SCB11-1600/10

6

2200

11700

0.85

60

820 x 820

SCB11-2000/10

6

2740

14400

0.70

62

820 x 820

SCB11-2500/10

6

3240

17100

0.70

62

820 x 820

 

Class F Insulation SCB12-315~2500/10

Rated High Voltage:10(10.5,11,6.6,6.3,6)kV

Rated Low Voltage:0.4kV

Vector Group: Dyn11or Yyn0

Insulation Level: Ll 75 AC 35 / Ll AC 3; Tap Range:±2*2.5%

Model

UK%

P0(W)

Pk(120ºC)(W)

I0%

LPA(AN)dB

Gauge m x n (mm)

SCB12-315/10

4

705

3470

1.0

55

660 x 660

SCB12-400/10

4

785

3990

1.0

55

660 x 660

SCB12-500/10

4

930

4880

1.0

57

660 x 660

SCB12-630/10

4

1070

5880

0.85

57

820 x 820

SCB12-630/10

6

1040

5960

0.85

57

820 x 820

SCB12-800/10

6

1210

6960

0.85

58

820 x 820

SCB12-1000/10

6

1410

8130

0.85

58

820 x 820

SCB12-1250/10

6

1670

9690

0.85

60

820 x 820

SCB12-1600/10

6

1960

11700

0.85

60

820 x 820

SCB12-2000/10

6

2440

14400

0.70

62

820 x 820

SCB12-2500/10

6

2880

17100

0.70

62

820 x 820



Cast Resin Transformer Designed for 6.3kv Primary Voltage UseCast Resin Transformer Designed for 6.3kv Primary Voltage UseCast Resin Transformer Designed for 6.3kv Primary Voltage Use

Equipment:


Slitting Line

Cast Resin Transformer Designed for 6.3kv Primary Voltage Use

Shearing Line
Cast Resin Transformer Designed for 6.3kv Primary Voltage Use

HEDRICH Vacuum Casting Tank
Cast Resin Transformer Designed for 6.3kv Primary Voltage Use

Curing Oven
Cast Resin Transformer Designed for 6.3kv Primary Voltage Use

Foil Winding
Cast Resin Transformer Designed for 6.3kv Primary Voltage Use

Testing Center
Cast Resin Transformer Designed for 6.3kv Primary Voltage Use
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now