Innovative Epoxy Resin Transformer for Enhanced Performance at 10kv

Product Details
Customization: Available
Application: Power
Phase: Three
Diamond Member Since 2020

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

High Repeat Buyers Choice
More than 50% of buyers repeatedly choose the supplier
Years of Export Experience
The export experience of the supplier is more than 10 years
Experienced Team
The supplier has 12 foreign trading staff(s) and 9 staff(s) with over 6 years of overseas trading experience
Patents Awarded
The supplier had awarded 2 patents, you can check the Audit Report for more information
to see all verified strength labels (30)
  • Innovative Epoxy Resin Transformer for Enhanced Performance at 10kv
  • Innovative Epoxy Resin Transformer for Enhanced Performance at 10kv
  • Innovative Epoxy Resin Transformer for Enhanced Performance at 10kv
  • Innovative Epoxy Resin Transformer for Enhanced Performance at 10kv
  • Innovative Epoxy Resin Transformer for Enhanced Performance at 10kv
  • Innovative Epoxy Resin Transformer for Enhanced Performance at 10kv
Find Similar Products

Basic Info.

Model NO.
SC(B)
Core
Core-type Transformer
Cooling Method
Dry-type Transformer
Winding Type
Multi-winding Transformer
Certification
ISO9001-2000, ISO9001, CE, ISO14001, ISO45001, ISO50001
Usage
Distribution Transformer
Frequency Characteristics
Power Frequency
Shape of Core
Ring
Brand
Ceeg
Rated Capacity
100-25000kVA
Primary Voltage
6/6.3/6.6/10/10.5/11/20/35kv
Secondary Voltage
11/10.5/6.3/6/3.15/0.4kv
Insulation Level
C, H, F
Frequency
50/60Hz
Impedance
4%/6%
Connection Symbol
Dyn11/Yyn0
Tapping Range
±2*2.5%/±5%
Standard
IEC60076
Core Material
Silicon Steel
Cooling Way
an/Af
Working Temperature
-20ºC~60ºC
Transport Package
International Wooden Case or According to Client′s
Trademark
CEEG
Origin
Jiangsu, China
HS Code
8504349000
Production Capacity
10000 Pieces/Year

Product Description

As the trailblazer in the Chinese market, we proudly became the first to achieve KEMA E2, C2, F1 certifications for our cutting-edge cast resin transformers.

CEEG's advanced cast resin dry-type transformers are a marvel of innovation, boasting numerous patents. Perfectly engineered for indoor environments that necessitate rigorous fire and explosion safety, these transformers also exhibit superior heat and moisture resistance, making them ideal for commercial centers, residential areas, hospitals, and factories. Our vacuum cast coil transformers are meticulously designed to excel in demanding outdoor settings, including petrochemical industries. With outstanding adaptability to seasonal load fluctuations and exceptional overload capacity, they stand out as the premier choice for encapsulated distribution transformers.

Optimal Working Environment
Designed to thrive in temperatures ranging from -20ºC to 60ºC;

Insulation

Material

expoxy resin class H / class C Nomex paper

Structure

 

HV coil is multi layer sectional cylinder structure, LV coil is foil with longitudinal air chamber structure.

Reliability

Insulation class

H(180ºC)

Tem. rise of coil

125K(normal 100K)

Over-load capacity

continuously 120%

Cooling method

AN/AF

 Environmental Protection

Noise

Low

Recycling

easy recycling and low pollution



Unparalleled Product Features

1. Exceptional reliability characterized by minimal loss and ultra-low partial discharge (less than 5PC), coupled with low acoustic emissions and robust thermal dissipation, ensuring endurance under 150% overload when forced air cooling is employed.

2. Superior moisture resistance, capable of seamless operation even in 100% humidity.

3. Impeccable safety standards, offering fire protection and eco-friendly operations, suitable for direct integration into load centers.

4. Incorporates a state-of-the-art temperature protection and control mechanism.

5. Maintenance-free design ensures ease of installation and minimizes overall operational expenses.



Showcase Export Case
Since 2014, we have proudly supplied the CEEG SCB and SC series cast resin dry-type transformers to LafargeHolcim. These transformers have been seamlessly integrated and continue to operate efficiently across LafargeHolcim's cement plants located in Nigeria, the Philippines, and Cameroon.


Innovative Epoxy Resin Transformer for Enhanced Performance at 10kv
Innovative Epoxy Resin Transformer for Enhanced Performance at 10kv
 

Class F Insulation SCB10-315~2500/10

Rated High Voltage:10(10.5,11,6.6,6.3,6)kV

Rated Low Voltage:0.4kV

Vector Group: Dyn11or Yyn0

Insulation Level: Ll 75 AC 35 / Ll AC 3; Tap Range:±2*2.5%

Model

UK%

P0(W)

Pk(120ºC)(W)

I0%

LPA(AN)dB

Gauge m x n (mm)

SCB10-315/10

4

880

3470

1.0

55

660 x 660

SCB10-400/10

4

980

3990

1.0

55

660 x 660

SCB10-500/10

4

1160

4880

1.0

57

660 x 660

SCB10-630/10

4

1340

5880

0.85

57

820 x 820

SCB10-630/10

6

1300

5960

0.85

57

820 x 820

SCB10-800/10

6

1520

6960

0.85

58

820 x 820

SCB10-1000/10

6

1770

8130

0.85

58

820 x 820

SCB10-1250/10

6

2090

9690

0.85

60

820 x 820

SCB10-1600/10

6

2450

11700

0.85

60

820 x 820

SCB10-2000/10

6

3050

14400

0.70

62

820 x 820

SCB10-2500/10

6

3600

17100

0.70

62

820 x 820

 

Class F Insulation SCB11-315~2500/10

Rated High Voltage:10(10.5,11,6.6,6.3,6)kV

Rated Low Voltage:0.4kV

Vector Group: Dyn11or Yyn0

Insulation Level: Ll 75 AC 35 / Ll AC 3; Tap Range:±2*2.5%

Model

UK%

P0(W)

Pk(120ºC)(W)

I0%

LPA(AN)dB

Gauge m x n (mm)

SCB11-315/10

4

790

3470

1.0

55

660 x 660

SCB11-400/10

4

880

3990

1.0

55

660 x 660

SCB11-500/10

4

1040

4880

1.0

57

660 x 660

SCB11-630/10

4

1200

5880

0.85

57

820 x 820

SCB11-630/10

6

1170

5960

0.85

57

820 x 820

SCB11-800/10

6

1360

6960

0.85

58

820 x 820

SCB11-1000/10

6

1590

8130

0.85

58

820 x 820

SCB11-1250/10

6

1880

9690

0.85

60

820 x 820

SCB11-1600/10

6

2200

11700

0.85

60

820 x 820

SCB11-2000/10

6

2740

14400

0.70

62

820 x 820

SCB11-2500/10

6

3240

17100

0.70

62

820 x 820

 

Class F Insulation SCB12-315~2500/10

Rated High Voltage:10(10.5,11,6.6,6.3,6)kV

Rated Low Voltage:0.4kV

Vector Group: Dyn11or Yyn0

Insulation Level: Ll 75 AC 35 / Ll AC 3; Tap Range:±2*2.5%

Model

UK%

P0(W)

Pk(120ºC)(W)

I0%

LPA(AN)dB

Gauge m x n (mm)

SCB12-315/10

4

705

3470

1.0

55

660 x 660

SCB12-400/10

4

785

3990

1.0

55

660 x 660

SCB12-500/10

4

930

4880

1.0

57

660 x 660

SCB12-630/10

4

1070

5880

0.85

57

820 x 820

SCB12-630/10

6

1040

5960

0.85

57

820 x 820

SCB12-800/10

6

1210

6960

0.85

58

820 x 820

SCB12-1000/10

6

1410

8130

0.85

58

820 x 820

SCB12-1250/10

6

1670

9690

0.85

60

820 x 820

SCB12-1600/10

6

1960

11700

0.85

60

820 x 820

SCB12-2000/10

6

2440

14400

0.70

62

820 x 820

SCB12-2500/10

6

2880

17100

0.70

62

820 x 820



Innovative Epoxy Resin Transformer for Enhanced Performance at 10kvInnovative Epoxy Resin Transformer for Enhanced Performance at 10kvInnovative Epoxy Resin Transformer for Enhanced Performance at 10kv

State-of-the-Art Equipment:


Precision Slitting Line

Innovative Epoxy Resin Transformer for Enhanced Performance at 10kv

High-Accuracy Shearing Line
Innovative Epoxy Resin Transformer for Enhanced Performance at 10kv

HEDRICH Cutting-Edge Vacuum Casting Tank
Innovative Epoxy Resin Transformer for Enhanced Performance at 10kv

Advanced Curing Oven
Innovative Epoxy Resin Transformer for Enhanced Performance at 10kv

Innovative Foil Winding
Innovative Epoxy Resin Transformer for Enhanced Performance at 10kv

Comprehensive Testing Center
Innovative Epoxy Resin Transformer for Enhanced Performance at 10kv
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now