Customization: | Available |
---|---|
Structure: | Protection |
Certification: | ISO9001:2000, CCC, CE, ISO14001, ISO45001, ISO50001 |
Suppliers with verified business licenses
Audited by an independent third-party inspection agency
Product Description
Introducing the CEEG compact substation, a marvel of engineering that seamlessly integrates high-voltage switchgear, distribution transformer, and low-voltage switchgear, making it the ideal solution for both indoor and outdoor applications. This substation is a powerhouse of innovation, featuring robust integration that minimizes spatial requirements, reduces initial investment costs, and simplifies both installation and maintenance procedures. With rated voltages available at 6KV, 10KV, and 35KV, and enclosure protection ratings of IP54 and IP33, this substation can be tailored to meet special requirements with custom solutions.
No. | Items | Unit | HV Switchgear | Transformer | LV Switchgear |
1 | Rated Voltage | kV | 10.5 | 10.5/0.4 | 0.4/0.23 |
2 | Rated Capacity | kVA | \ | 800 | |
3 | Rated Current | A | 20-200 | 100-4000 | |
4 | Short Circuit Interrupting Current | kA | 31.5,50 | \ | 30-50 |
5 | Short Circuit Makring Current | kA | 50 | \ | |
6 | Dynamic Stable Current | kA | \ | \ | |
7 | Thermal Stable Current | kA/S | 10-20kA/4s | \ | 15~65x1 |
8 | PFWV Between Phases, to earth/isolation contacts | kV/min | 42 | 35 | 2.5~2 |
9 | Lightning Strike (full-wave) | kV | 75/85 | \ | \ |
10 | Housing Proof Class | IP43 | |||
11 | Sound Level | dB | <55 |
Product Features
Outstanding Production Performance: The frame boasts a special protective paint coating, while the internal design incorporates advanced safety measures to effectively prevent:
the incorrect operation of circuit breakers.
the switching of isolators under load conditions.
the connection of grounding wires (grounding switches) while the system is energized.
the closing of circuit breakers when grounding wires (grounding switches) are in place.
unintended entry into live compartments.
Harnessing the power of BIOSCO technology, this substation features a modular structure that ensures ease of installation and operation.
Constructed from finely welded structural steel, it delivers exceptional mechanical strength and a surface treated for superior resistance to the elements.
Advanced Environmental Control: Equipped with automatic temperature control devices, the transformer and low-voltage rooms maintain optimal temperature and ventilation for enhanced performance.
The top insulation layer effectively prevents condensation due to rapid temperature changes, with additional insulation options available for the enclosure.
Smart Operations: Experience the future with intelligent operation and maintenance, featuring smart data collection and analysis on HV & LV switchgear and transformers.
Design and Customization: With an appealing design and customizable options, this substation offers a diverse range of choices. The internal structure can be configured in 'H' and 'T' shapes, with corridor and non-corridor layouts to suit various needs.
Enclosure Structure
High Voltage Chamber:
Within the primary high voltage chamber, you will find a sophisticated high-voltage ring main unit. Featuring cutting-edge sulfur hexafluoride load switches and vacuum circuit breakers, the high-voltage cabinet ensures the transformer's safety against short circuits and overloads.
Transformer Chamber:
The three-phase transformer chamber is versatile, accommodating both dry-type and oil-immersed transformers. It includes a state-of-the-art ventilation system with adjustable temperature settings and live space barriers to prevent accidental contact during inspection.
Low Voltage Chamber:
This secondary low voltage chamber is available in two configurations: with or without a corridor. It can house an array of cabinets, including metering, main incoming, outgoing, capacitor, and interlocking cabinets for dual transformers, ensuring comprehensive low-voltage switchgear functionality. Capacitive reactive power compensation ranges from 15% to 30% of the transformer's capacity, providing optimal performance.
Operating Environment
Ambient Temperature: Suitable for conditions ranging from -25°C to 40°C
Altitude: Effective operation at altitudes not exceeding 1000 meters
Relative Humidity: Maintains performance with humidity not exceeding 90% at 25°C, with short-term peaks up to 100%
Installation Conditions: Ideal for environments free from fire, explosion hazards, chemical corrosion, and severe vibrations, ensuring safe and stable operations.