Fire-Resistant Cast Resin Transformer

Product Details
Customization: Available
Application: Power
Phase: Three
Diamond Member Since 2020

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

High Repeat Buyers Choice
More than 50% of buyers repeatedly choose the supplier
Years of Export Experience
The export experience of the supplier is more than 10 years
Experienced Team
The supplier has 12 foreign trading staff(s) and 9 staff(s) with over 6 years of overseas trading experience
Patents Awarded
The supplier had awarded 2 patents, you can check the Audit Report for more information
to see all verified strength labels (30)
  • Fire-Resistant Cast Resin Transformer
  • Fire-Resistant Cast Resin Transformer
  • Fire-Resistant Cast Resin Transformer
  • Fire-Resistant Cast Resin Transformer
  • Fire-Resistant Cast Resin Transformer
  • Fire-Resistant Cast Resin Transformer
Find Similar Products

Basic Info.

Model NO.
SC(B)
Core
Core-type Transformer
Cooling Method
Dry-type Transformer
Winding Type
Multi-winding Transformer
Certification
ISO9001-2000, ISO9001, CE, ISO14001, ISO45001, ISO50001
Usage
Distribution Transformer
Frequency Characteristics
Power Frequency
Shape of Core
Ring
Brand
Ceeg
Rated Capacity
100-25000kVA
Primary Voltage
6/6.3/6.6/10/10.5/11/20/35kv
Secondary Voltage
11/10.5/6.3/6/3.15/0.4kv
Insulation Level
C, H, F
Frequency
50/60Hz
Impedance
4%/6%
Connection Symbol
Dyn11/Yyn0
Tapping Range
±2*2.5%/±5%
Standard
IEC60076
Core Material
Silicon Steel
Cooling Way
an/Af
Working Temperature
-20ºC~60ºC
Transport Package
International Wooden Case or According to Client′s
Trademark
CEEG
Origin
Jiangsu, China
HS Code
8504349000
Production Capacity
10000 Pieces/Year

Product Description

Emerging as the pioneering company in China to achieve the prestigious KEMA E2, C2, F1 certification for its cast resin transformers.

The innovative CEEG cast resin dry-type transformer is an epitome of engineering excellence, adorned with numerous patents. This product is a perfect fit for indoor environments that necessitate exceptional fire and explosion protection, along with superior resilience to high temperatures and moisture. It is ideally suited for commercial centers, residential complexes, hospitals, and manufacturing facilities. Its vacuum cast coil design is engineered to meet stringent standards even in challenging outdoor settings like those in petrochemical industries. Additionally, it features superb resilience to seasonal load fluctuations and overload affinities, making it an optimal choice for encapsulated distribution transformers.

Working Environment
Temperature range: -20ºC to 60ºC;

Insulation

Material

expoxy resin class H / class C Nomex paper

Structure

 

HV coil is multi layer sectional cylinder structure, LV coil is foil with longitudinal air chamber structure.

Reliability

Insulation class

H(180ºC)

Tem. rise of coil

125K(normal 100K)

Over-load capacity

continuously 120%

Cooling method

AN/AF

 Environmental Protection

Noise

Low

Recycling

easy recycling and low pollution



Product Features

1. Exhibits unparalleled reliability with minimized losses and partial discharge (below 5PC), operates with low noise, and has an efficient heat dissipation capacity, capable of withstanding a 150% overload under forced air cooling conditions.

2. Demonstrates excellent moisture resistance, functioning seamlessly in environments with 100% humidity.

3. Ensures safety with fire protection and pollution-free operations, making it apt for direct installation within load centers.

4. Comes integrated with a sophisticated temperature protection and control system.

5. Offers seamless, maintenance-free operation, easy installation, and reduced overall operating costs.



Export Case
In 2014, we initiated the supply of the CEEG SCB and SC series cast resin dry-type transformers to LafargeHolcim. This partnership has flourished, with our transformers successfully installed and operating in LafargeHolcim's cement plants across Nigeria, the Philippines, and Cameroon.


Fire-Resistant Cast Resin Transformer
Fire-Resistant Cast Resin Transformer
 

Class F Insulation SCB10-315~2500/10

Rated High Voltage:10(10.5,11,6.6,6.3,6)kV

Rated Low Voltage:0.4kV

Vector Group: Dyn11or Yyn0

Insulation Level: Ll 75 AC 35 / Ll AC 3; Tap Range:±2*2.5%

Model

UK%

P0(W)

Pk(120ºC)(W)

I0%

LPA(AN)dB

Gauge m x n (mm)

SCB10-315/10

4

880

3470

1.0

55

660 x 660

SCB10-400/10

4

980

3990

1.0

55

660 x 660

SCB10-500/10

4

1160

4880

1.0

57

660 x 660

SCB10-630/10

4

1340

5880

0.85

57

820 x 820

SCB10-630/10

6

1300

5960

0.85

57

820 x 820

SCB10-800/10

6

1520

6960

0.85

58

820 x 820

SCB10-1000/10

6

1770

8130

0.85

58

820 x 820

SCB10-1250/10

6

2090

9690

0.85

60

820 x 820

SCB10-1600/10

6

2450

11700

0.85

60

820 x 820

SCB10-2000/10

6

3050

14400

0.70

62

820 x 820

SCB10-2500/10

6

3600

17100

0.70

62

820 x 820

 

Class F Insulation SCB11-315~2500/10

Rated High Voltage:10(10.5,11,6.6,6.3,6)kV

Rated Low Voltage:0.4kV

Vector Group: Dyn11or Yyn0

Insulation Level: Ll 75 AC 35 / Ll AC 3; Tap Range:±2*2.5%

Model

UK%

P0(W)

Pk(120ºC)(W)

I0%

LPA(AN)dB

Gauge m x n (mm)

SCB11-315/10

4

790

3470

1.0

55

660 x 660

SCB11-400/10

4

880

3990

1.0

55

660 x 660

SCB11-500/10

4

1040

4880

1.0

57

660 x 660

SCB11-630/10

4

1200

5880

0.85

57

820 x 820

SCB11-630/10

6

1170

5960

0.85

57

820 x 820

SCB11-800/10

6

1360

6960

0.85

58

820 x 820

SCB11-1000/10

6

1590

8130

0.85

58

820 x 820

SCB11-1250/10

6

1880

9690

0.85

60

820 x 820

SCB11-1600/10

6

2200

11700

0.85

60

820 x 820

SCB11-2000/10

6

2740

14400

0.70

62

820 x 820

SCB11-2500/10

6

3240

17100

0.70

62

820 x 820

 

Class F Insulation SCB12-315~2500/10

Rated High Voltage:10(10.5,11,6.6,6.3,6)kV

Rated Low Voltage:0.4kV

Vector Group: Dyn11or Yyn0

Insulation Level: Ll 75 AC 35 / Ll AC 3; Tap Range:±2*2.5%

Model

UK%

P0(W)

Pk(120ºC)(W)

I0%

LPA(AN)dB

Gauge m x n (mm)

SCB12-315/10

4

705

3470

1.0

55

660 x 660

SCB12-400/10

4

785

3990

1.0

55

660 x 660

SCB12-500/10

4

930

4880

1.0

57

660 x 660

SCB12-630/10

4

1070

5880

0.85

57

820 x 820

SCB12-630/10

6

1040

5960

0.85

57

820 x 820

SCB12-800/10

6

1210

6960

0.85

58

820 x 820

SCB12-1000/10

6

1410

8130

0.85

58

820 x 820

SCB12-1250/10

6

1670

9690

0.85

60

820 x 820

SCB12-1600/10

6

1960

11700

0.85

60

820 x 820

SCB12-2000/10

6

2440

14400

0.70

62

820 x 820

SCB12-2500/10

6

2880

17100

0.70

62

820 x 820



Fire-Resistant Cast Resin TransformerFire-Resistant Cast Resin TransformerFire-Resistant Cast Resin Transformer

Equipment:


Slitting Line

Fire-Resistant Cast Resin Transformer

Shearing Line
Fire-Resistant Cast Resin Transformer

HEDRICH Vacuum Casting Tank
Fire-Resistant Cast Resin Transformer

Curing Oven
Fire-Resistant Cast Resin Transformer

Foil Winding
Fire-Resistant Cast Resin Transformer

Testing Center
Fire-Resistant Cast Resin Transformer
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now