  • Cast Resin Dry Type Transformer with High Insulation Class
  • Cast Resin Dry Type Transformer with High Insulation Class
  • Cast Resin Dry Type Transformer with High Insulation Class
  • Cast Resin Dry Type Transformer with High Insulation Class
  • Cast Resin Dry Type Transformer with High Insulation Class
  • Cast Resin Dry Type Transformer with High Insulation Class
Find Similar Products

Basic Info.

Model NO.
SC(B)
Core
Core-type Transformer
Cooling Method
Dry-type Transformer
Winding Type
Multi-winding Transformer
Certification
ISO9001-2000, ISO9001, CE, ISO14001, ISO45001, ISO50001
Usage
Distribution Transformer
Frequency Characteristics
Power Frequency
Shape of Core
Ring
Brand
Ceeg
Rated Capacity
100-25000kVA
Primary Voltage
6/6.3/6.6/10/10.5/11/20/35kv
Secondary Voltage
11/10.5/6.3/6/3.15/0.4kv
Insulation Level
C, H, F
Frequency
50/60Hz
Impedance
4%/6%
Connection Symbol
Dyn11/Yyn0
Tapping Range
±2*2.5%/±5%
Standard
IEC60076
Core Material
Silicon Steel
Cooling Way
an/Af
Working Temperature
-20ºC~60ºC
Transport Package
International Wooden Case or According to Client′s
Trademark
CEEG
Origin
Jiangsu, China
HS Code
8504349000
Production Capacity
10000 Pieces/Year

Product Description

Pioneering the industry, China Electric Equipment (Jiangsu) Transformer Manufacture Co., Ltd. became the first company in China to successfully pass the esteemed KEMA E2, C2, F1 certification tests for cast resin transformers, setting a benchmark for excellence in quality and safety.

CEEG's innovative cast resin dry-type transformers are protected by numerous patents, showcasing a commitment to technological advancement. Ideally suited for indoor environments where fire and explosion protection is paramount, these transformers excel in high temperature and moisture conditions. From bustling commercial centers and tranquil residential areas to critical infrastructure like hospitals and dynamic factories, their versatility is unmatched. Engineered to meet the exacting standards of special outdoor environments such as petrochemical enterprises, they also demonstrate impressive resilience to seasonal load variations and overload conditions. This makes them the prime choice for selecting encapsulated distribution transformers.

Optimal Working Environment
Designed for varied conditions, they operate seamlessly at temperatures ranging from -20ºC to 60ºC, accommodating diverse climate demands.

Insulation

Material

expoxy resin class H / class C Nomex paper

Structure

 

HV coil is multi layer sectional cylinder structure, LV coil is foil with longitudinal air chamber structure.

Reliability

Insulation class

H(180ºC)

Tem. rise of coil

125K(normal 100K)

Over-load capacity

continuously 120%

Cooling method

AN/AF

 Environmental Protection

Noise

Low

Recycling

easy recycling and low pollution



Exceptional Product Features

1. Renowned for high reliability and efficiency, these transformers feature minimal loss, minimal partial discharge (under 5PC), low noise output, and superior heat dissipation, capable of enduring up to 150% overload with forced air cooling.

2. Unmatched performance in moisture-rich environments, operating effectively even in 100% humidity.

3. Prioritizing safety, these units offer fire protection and pollution-free operation, perfectly suited for direct installation in load centers.

4. Comes with an all-encompassing temperature protection and control system, ensuring operational safety.

5. Enjoy maintenance-free operation, easy installation, and reduced overall operating costs, optimizing your investment.



Export Success Story
Since 2014, we have proudly supplied the CEEG SCB and SC series cast resin dry-type transformers to LafargeHolcim, with installations in their cement plants across Nigeria, the Philippines, and Cameroon. This ongoing partnership underscores the reliability and performance of our products.


Cast Resin Dry Type Transformer with High Insulation Class
Cast Resin Dry Type Transformer with High Insulation Class
 

Class F Insulation SCB10-315~2500/10

Rated High Voltage:10(10.5,11,6.6,6.3,6)kV

Rated Low Voltage:0.4kV

Vector Group: Dyn11or Yyn0

Insulation Level: Ll 75 AC 35 / Ll AC 3; Tap Range:±2*2.5%

Model

UK%

P0(W)

Pk(120ºC)(W)

I0%

LPA(AN)dB

Gauge m x n (mm)

SCB10-315/10

4

880

3470

1.0

55

660 x 660

SCB10-400/10

4

980

3990

1.0

55

660 x 660

SCB10-500/10

4

1160

4880

1.0

57

660 x 660

SCB10-630/10

4

1340

5880

0.85

57

820 x 820

SCB10-630/10

6

1300

5960

0.85

57

820 x 820

SCB10-800/10

6

1520

6960

0.85

58

820 x 820

SCB10-1000/10

6

1770

8130

0.85

58

820 x 820

SCB10-1250/10

6

2090

9690

0.85

60

820 x 820

SCB10-1600/10

6

2450

11700

0.85

60

820 x 820

SCB10-2000/10

6

3050

14400

0.70

62

820 x 820

SCB10-2500/10

6

3600

17100

0.70

62

820 x 820

 

Class F Insulation SCB11-315~2500/10

Rated High Voltage:10(10.5,11,6.6,6.3,6)kV

Rated Low Voltage:0.4kV

Vector Group: Dyn11or Yyn0

Insulation Level: Ll 75 AC 35 / Ll AC 3; Tap Range:±2*2.5%

Model

UK%

P0(W)

Pk(120ºC)(W)

I0%

LPA(AN)dB

Gauge m x n (mm)

SCB11-315/10

4

790

3470

1.0

55

660 x 660

SCB11-400/10

4

880

3990

1.0

55

660 x 660

SCB11-500/10

4

1040

4880

1.0

57

660 x 660

SCB11-630/10

4

1200

5880

0.85

57

820 x 820

SCB11-630/10

6

1170

5960

0.85

57

820 x 820

SCB11-800/10

6

1360

6960

0.85

58

820 x 820

SCB11-1000/10

6

1590

8130

0.85

58

820 x 820

SCB11-1250/10

6

1880

9690

0.85

60

820 x 820

SCB11-1600/10

6

2200

11700

0.85

60

820 x 820

SCB11-2000/10

6

2740

14400

0.70

62

820 x 820

SCB11-2500/10

6

3240

17100

0.70

62

820 x 820

 

Class F Insulation SCB12-315~2500/10

Rated High Voltage:10(10.5,11,6.6,6.3,6)kV

Rated Low Voltage:0.4kV

Vector Group: Dyn11or Yyn0

Insulation Level: Ll 75 AC 35 / Ll AC 3; Tap Range:±2*2.5%

Model

UK%

P0(W)

Pk(120ºC)(W)

I0%

LPA(AN)dB

Gauge m x n (mm)

SCB12-315/10

4

705

3470

1.0

55

660 x 660

SCB12-400/10

4

785

3990

1.0

55

660 x 660

SCB12-500/10

4

930

4880

1.0

57

660 x 660

SCB12-630/10

4

1070

5880

0.85

57

820 x 820

SCB12-630/10

6

1040

5960

0.85

57

820 x 820

SCB12-800/10

6

1210

6960

0.85

58

820 x 820

SCB12-1000/10

6

1410

8130

0.85

58

820 x 820

SCB12-1250/10

6

1670

9690

0.85

60

820 x 820

SCB12-1600/10

6

1960

11700

0.85

60

820 x 820

SCB12-2000/10

6

2440

14400

0.70

62

820 x 820

SCB12-2500/10

6

2880

17100

0.70

62

820 x 820



Cast Resin Dry Type Transformer with High Insulation ClassCast Resin Dry Type Transformer with High Insulation ClassCast Resin Dry Type Transformer with High Insulation Class

Advanced Equipment Utilized:


Precision Slitting Line

Cast Resin Dry Type Transformer with High Insulation Class

High-Performance Shearing Line
Cast Resin Dry Type Transformer with High Insulation Class

HEDRICH Vacuum Casting Tank for superior cast quality
Cast Resin Dry Type Transformer with High Insulation Class

Efficient Curing Oven
Cast Resin Dry Type Transformer with High Insulation Class

Foil Winding for enhanced durability
Cast Resin Dry Type Transformer with High Insulation Class

Comprehensive Testing Center ensuring quality assurance
Cast Resin Dry Type Transformer with High Insulation Class
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now