Low Loss Epoxy Resin Distribution Transformer for Primary Voltage up to 35kv

Product Details
Customization: Available
Application: Power
Phase: Three
Diamond Member Since 2020

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

High Repeat Buyers Choice
More than 50% of buyers repeatedly choose the supplier
Years of Export Experience
The export experience of the supplier is more than 10 years
Experienced Team
The supplier has 12 foreign trading staff(s) and 9 staff(s) with over 6 years of overseas trading experience
Patents Awarded
The supplier had awarded 2 patents, you can check the Audit Report for more information
to see all verified strength labels (30)
  • Low Loss Epoxy Resin Distribution Transformer for Primary Voltage up to 35kv
  • Low Loss Epoxy Resin Distribution Transformer for Primary Voltage up to 35kv
  • Low Loss Epoxy Resin Distribution Transformer for Primary Voltage up to 35kv
  • Low Loss Epoxy Resin Distribution Transformer for Primary Voltage up to 35kv
  • Low Loss Epoxy Resin Distribution Transformer for Primary Voltage up to 35kv
  • Low Loss Epoxy Resin Distribution Transformer for Primary Voltage up to 35kv
Find Similar Products

Basic Info.

Model NO.
SC(B)
Cooling Method
Dry-type Transformer
Winding Type
Multi-winding Transformer
Certification
ISO9001-2000, ISO9001, CE, ISO14001, ISO45001, ISO50001
Usage
Distribution Transformer
Frequency Characteristics
Power Frequency
Shape of Core
Ring
Brand
Ceeg
Rated Capacity
100-25000kVA
Primary Voltage
6/6.3/6.6/10/10.5/11/20/35kv
Secondary Voltage
11/10.5/6.3/6/3.15/0.4kv
Insulation Level
C, H, F
Frequency
50/60Hz
Impedance
4%/6%
Connection Symbol
Dyn11/Yyn0
Tapping Range
±2*2.5%/±5%
Standard
IEC60076
Core Material
Silicon Steel
Cooling Way
an/Af
Working Temperature
-20ºC~60ºC
Transport Package
International Wooden Case or According to Client′s
Trademark
CEEG
Origin
Jiangsu, China
HS Code
8504349000
Production Capacity
10000 Pieces/Year

Product Description

Pioneering the path in China, we're proud to be the first company to successfully achieve the prestigious KEMA E2, C2, F1 certifications for our cast resin transformers-an accolade that underscores our commitment to quality and innovation.

CEEG's state-of-the-art cast resin dry-type transformers are a testament to our innovation, adorned with numerous patents. These transformers are perfectly tailored for indoor environments that prioritize fire and explosion safety, as well as robust performance against high temperatures and humidity. They excel in commercial centers, residential complexes, hospitals, and factories, offering unparalleled reliability. Additionally, our vacuum cast coil transformers are engineered to meet the stringent demands of outdoor environments like petrochemical enterprises. They boast exceptional resilience against seasonal load fluctuations and overloads, making them the premier choice for encapsulated distribution transformers.

Optimal Working Environment
Our transformers operate efficiently in a temperature range from -20ºC to 60ºC, ensuring performance stability across diverse conditions.

Insulation

Material

expoxy resin class H / class C Nomex paper

Structure

 

HV coil is multi layer sectional cylinder structure, LV coil is foil with longitudinal air chamber structure.

Reliability

Insulation class

H(180ºC)

Tem. rise of coil

125K(normal 100K)

Over-load capacity

continuously 120%

Cooling method

AN/AF

 Environmental Protection

Noise

Low

Recycling

easy recycling and low pollution



Distinguished Product Features

1. Our transformers stand out with their exceptional reliability, characterized by minimal loss, low partial discharge (less than 5PC), whisper-quiet operation, and superior heat dissipation. They are built to handle 150% overload in forced air cooling scenarios effortlessly.

2. With superior moisture-resistant capabilities, they are engineered to operate seamlessly even in 100% humidity environments, ensuring durability and consistency.

3. Emphasizing safety and environmental consciousness, they are fire-resistant and pollution-free, making them ideal for direct installation in load centers.

4. They are fitted with an advanced temperature protection and control system, enhancing their operational safety and longevity.

5. These transformers are designed to be maintenance-free, simple to install, and provide a cost-effective solution with low overall operating expenses.



Global Export Success
Since 2014, we've proudly supplied the esteemed CEEG SCB and SC series of cast resin dry-type transformers to LafargeHolcim. These engineering marvels have been seamlessly integrated and are performing exceptionally well in LafargeHolcim's cement plants located in Nigeria, the Philippines, and Cameroon, strengthening our international presence and reliability.


Low Loss Epoxy Resin Distribution Transformer for Primary Voltage up to 35kv
Low Loss Epoxy Resin Distribution Transformer for Primary Voltage up to 35kv
 

Class F Insulation SCB10-315~2500/10

Rated High Voltage:10(10.5,11,6.6,6.3,6)kV

Rated Low Voltage:0.4kV

Vector Group: Dyn11or Yyn0

Insulation Level: Ll 75 AC 35 / Ll AC 3; Tap Range:±2*2.5%

Model

UK%

P0(W)

Pk(120ºC)(W)

I0%

LPA(AN)dB

Gauge m x n (mm)

SCB10-315/10

4

880

3470

1.0

55

660 x 660

SCB10-400/10

4

980

3990

1.0

55

660 x 660

SCB10-500/10

4

1160

4880

1.0

57

660 x 660

SCB10-630/10

4

1340

5880

0.85

57

820 x 820

SCB10-630/10

6

1300

5960

0.85

57

820 x 820

SCB10-800/10

6

1520

6960

0.85

58

820 x 820

SCB10-1000/10

6

1770

8130

0.85

58

820 x 820

SCB10-1250/10

6

2090

9690

0.85

60

820 x 820

SCB10-1600/10

6

2450

11700

0.85

60

820 x 820

SCB10-2000/10

6

3050

14400

0.70

62

820 x 820

SCB10-2500/10

6

3600

17100

0.70

62

820 x 820

 

Class F Insulation SCB11-315~2500/10

Rated High Voltage:10(10.5,11,6.6,6.3,6)kV

Rated Low Voltage:0.4kV

Vector Group: Dyn11or Yyn0

Insulation Level: Ll 75 AC 35 / Ll AC 3; Tap Range:±2*2.5%

Model

UK%

P0(W)

Pk(120ºC)(W)

I0%

LPA(AN)dB

Gauge m x n (mm)

SCB11-315/10

4

790

3470

1.0

55

660 x 660

SCB11-400/10

4

880

3990

1.0

55

660 x 660

SCB11-500/10

4

1040

4880

1.0

57

660 x 660

SCB11-630/10

4

1200

5880

0.85

57

820 x 820

SCB11-630/10

6

1170

5960

0.85

57

820 x 820

SCB11-800/10

6

1360

6960

0.85

58

820 x 820

SCB11-1000/10

6

1590

8130

0.85

58

820 x 820

SCB11-1250/10

6

1880

9690

0.85

60

820 x 820

SCB11-1600/10

6

2200

11700

0.85

60

820 x 820

SCB11-2000/10

6

2740

14400

0.70

62

820 x 820

SCB11-2500/10

6

3240

17100

0.70

62

820 x 820

 

Class F Insulation SCB12-315~2500/10

Rated High Voltage:10(10.5,11,6.6,6.3,6)kV

Rated Low Voltage:0.4kV

Vector Group: Dyn11or Yyn0

Insulation Level: Ll 75 AC 35 / Ll AC 3; Tap Range:±2*2.5%

Model

UK%

P0(W)

Pk(120ºC)(W)

I0%

LPA(AN)dB

Gauge m x n (mm)

SCB12-315/10

4

705

3470

1.0

55

660 x 660

SCB12-400/10

4

785

3990

1.0

55

660 x 660

SCB12-500/10

4

930

4880

1.0

57

660 x 660

SCB12-630/10

4

1070

5880

0.85

57

820 x 820

SCB12-630/10

6

1040

5960

0.85

57

820 x 820

SCB12-800/10

6

1210

6960

0.85

58

820 x 820

SCB12-1000/10

6

1410

8130

0.85

58

820 x 820

SCB12-1250/10

6

1670

9690

0.85

60

820 x 820

SCB12-1600/10

6

1960

11700

0.85

60

820 x 820

SCB12-2000/10

6

2440

14400

0.70

62

820 x 820

SCB12-2500/10

6

2880

17100

0.70

62

820 x 820



Low Loss Epoxy Resin Distribution Transformer for Primary Voltage up to 35kvLow Loss Epoxy Resin Distribution Transformer for Primary Voltage up to 35kvLow Loss Epoxy Resin Distribution Transformer for Primary Voltage up to 35kv

Cutting-Edge Equipment:


Precision Slitting Line

Low Loss Epoxy Resin Distribution Transformer for Primary Voltage up to 35kv

Efficient Shearing Line
Low Loss Epoxy Resin Distribution Transformer for Primary Voltage up to 35kv

HEDRICH Vacuum Casting Tank for superior quality and consistency
Low Loss Epoxy Resin Distribution Transformer for Primary Voltage up to 35kv

Advanced Curing Oven for optimal performance
Low Loss Epoxy Resin Distribution Transformer for Primary Voltage up to 35kv

Innovative Foil Winding technology
Low Loss Epoxy Resin Distribution Transformer for Primary Voltage up to 35kv

Comprehensive Testing Center to ensure the highest standards
Low Loss Epoxy Resin Distribution Transformer for Primary Voltage up to 35kv
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now