High Efficiency Cast Resin Transformer for 0.4~11 Kv Second Voltage

Product Details
Customization: Available
Application: Power
Phase: Three
Diamond Member Since 2020

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

High Repeat Buyers Choice
More than 50% of buyers repeatedly choose the supplier
Years of Export Experience
The export experience of the supplier is more than 10 years
Experienced Team
The supplier has 12 foreign trading staff(s) and 9 staff(s) with over 6 years of overseas trading experience
Patents Awarded
The supplier had awarded 2 patents, you can check the Audit Report for more information
to see all verified strength labels (30)
  • High Efficiency Cast Resin Transformer for 0.4~11 Kv Second Voltage
  • High Efficiency Cast Resin Transformer for 0.4~11 Kv Second Voltage
  • High Efficiency Cast Resin Transformer for 0.4~11 Kv Second Voltage
  • High Efficiency Cast Resin Transformer for 0.4~11 Kv Second Voltage
  • High Efficiency Cast Resin Transformer for 0.4~11 Kv Second Voltage
  • High Efficiency Cast Resin Transformer for 0.4~11 Kv Second Voltage
Find Similar Products

Basic Info.

Model NO.
SC(B)
Core
Core-type Transformer
Cooling Method
Dry-type Transformer
Winding Type
Multi-winding Transformer
Certification
ISO9001-2000, ISO9001, CE, ISO14001, ISO45001, ISO50001
Usage
Distribution Transformer
Frequency Characteristics
Power Frequency
Shape of Core
Ring
Brand
Ceeg
Rated Capacity
100-25000kVA
Primary Voltage
6/6.3/6.6/10/10.5/11/20/35kv
Secondary Voltage
11/10.5/6.3/6/3.15/0.4kv
Insulation Level
C, H, F
Frequency
50/60Hz
Impedance
4%/6%
Connection Symbol
Dyn11/Yyn0
Tapping Range
±2*2.5%/±5%
Standard
IEC60076
Core Material
Silicon Steel
Cooling Way
an/Af
Working Temperature
-20ºC~60ºC
Transport Package
International Wooden Case or According to Client′s
Trademark
CEEG
Origin
Jiangsu, China
HS Code
8504349000
Production Capacity
10000 Pieces/Year

Product Description

Pioneers in the nation, we proudly became the first Chinese company to successfully pass the esteemed KEMA E2, C2, F1 tests for our world-class cast resin transformers.

CEEG's innovative cast resin dry-type transformer is a marvel of engineering, boasting numerous patents. This product is impeccably crafted for indoor environments where fire and explosion safety, as well as high resistance to temperature and moisture, are essential. Perfect for commercial centers, residential zones, hospitals, and factories, our vacuum cast coil transformer is also built to excel in demanding outdoor settings like petrochemical sites. Its exceptional durability against seasonal loads and overload scenarios makes it the ideal choice for encapsulated distribution transformers.

Operational Environment
Capable of thriving in temperatures ranging from -20ºC to 60ºC;

Insulation

Material

expoxy resin class H / class C Nomex paper

Structure

 

HV coil is multi layer sectional cylinder structure, LV coil is foil with longitudinal air chamber structure.

Reliability

Insulation class

H(180ºC)

Tem. rise of coil

125K(normal 100K)

Over-load capacity

continuously 120%

Cooling method

AN/AF

 Environmental Protection

Noise

Low

Recycling

easy recycling and low pollution



Unparalleled Product Attributes

1. Engineered for supreme reliability, featuring minimal loss, low partial discharge (under 5PC), minimal noise, and superior heat dissipation, supporting up to 150% overload when in forced air cooling mode.

2. Exceptional performance in moisture-laden conditions, withstanding operation in full 100% humidity.

3. Committed to safety with fire protection and eco-friendly, pollution-free operations, perfect for placement directly in load centers.

4. Comes with an advanced temperature protection and management system.

5. Designed to be maintenance-free, easy to install, and offers cost-effective operation over its lifecycle.



International Success Story
In 2014, we embarked on supplying the CEEG SCB and SC series of cast resin dry-type transformers to LafargeHolcim, marking the beginning of a thriving partnership. These transformers have proven their mettle, operating seamlessly in LafargeHolcim's cement plants across Nigeria, the Philippines, and Cameroon.


High Efficiency Cast Resin Transformer for 0.4~11 Kv Second Voltage
High Efficiency Cast Resin Transformer for 0.4~11 Kv Second Voltage
 

Class F Insulation SCB10-315~2500/10

Rated High Voltage:10(10.5,11,6.6,6.3,6)kV

Rated Low Voltage:0.4kV

Vector Group: Dyn11or Yyn0

Insulation Level: Ll 75 AC 35 / Ll AC 3; Tap Range:±2*2.5%

Model

UK%

P0(W)

Pk(120ºC)(W)

I0%

LPA(AN)dB

Gauge m x n (mm)

SCB10-315/10

4

880

3470

1.0

55

660 x 660

SCB10-400/10

4

980

3990

1.0

55

660 x 660

SCB10-500/10

4

1160

4880

1.0

57

660 x 660

SCB10-630/10

4

1340

5880

0.85

57

820 x 820

SCB10-630/10

6

1300

5960

0.85

57

820 x 820

SCB10-800/10

6

1520

6960

0.85

58

820 x 820

SCB10-1000/10

6

1770

8130

0.85

58

820 x 820

SCB10-1250/10

6

2090

9690

0.85

60

820 x 820

SCB10-1600/10

6

2450

11700

0.85

60

820 x 820

SCB10-2000/10

6

3050

14400

0.70

62

820 x 820

SCB10-2500/10

6

3600

17100

0.70

62

820 x 820

 

Class F Insulation SCB11-315~2500/10

Rated High Voltage:10(10.5,11,6.6,6.3,6)kV

Rated Low Voltage:0.4kV

Vector Group: Dyn11or Yyn0

Insulation Level: Ll 75 AC 35 / Ll AC 3; Tap Range:±2*2.5%

Model

UK%

P0(W)

Pk(120ºC)(W)

I0%

LPA(AN)dB

Gauge m x n (mm)

SCB11-315/10

4

790

3470

1.0

55

660 x 660

SCB11-400/10

4

880

3990

1.0

55

660 x 660

SCB11-500/10

4

1040

4880

1.0

57

660 x 660

SCB11-630/10

4

1200

5880

0.85

57

820 x 820

SCB11-630/10

6

1170

5960

0.85

57

820 x 820

SCB11-800/10

6

1360

6960

0.85

58

820 x 820

SCB11-1000/10

6

1590

8130

0.85

58

820 x 820

SCB11-1250/10

6

1880

9690

0.85

60

820 x 820

SCB11-1600/10

6

2200

11700

0.85

60

820 x 820

SCB11-2000/10

6

2740

14400

0.70

62

820 x 820

SCB11-2500/10

6

3240

17100

0.70

62

820 x 820

 

Class F Insulation SCB12-315~2500/10

Rated High Voltage:10(10.5,11,6.6,6.3,6)kV

Rated Low Voltage:0.4kV

Vector Group: Dyn11or Yyn0

Insulation Level: Ll 75 AC 35 / Ll AC 3; Tap Range:±2*2.5%

Model

UK%

P0(W)

Pk(120ºC)(W)

I0%

LPA(AN)dB

Gauge m x n (mm)

SCB12-315/10

4

705

3470

1.0

55

660 x 660

SCB12-400/10

4

785

3990

1.0

55

660 x 660

SCB12-500/10

4

930

4880

1.0

57

660 x 660

SCB12-630/10

4

1070

5880

0.85

57

820 x 820

SCB12-630/10

6

1040

5960

0.85

57

820 x 820

SCB12-800/10

6

1210

6960

0.85

58

820 x 820

SCB12-1000/10

6

1410

8130

0.85

58

820 x 820

SCB12-1250/10

6

1670

9690

0.85

60

820 x 820

SCB12-1600/10

6

1960

11700

0.85

60

820 x 820

SCB12-2000/10

6

2440

14400

0.70

62

820 x 820

SCB12-2500/10

6

2880

17100

0.70

62

820 x 820



High Efficiency Cast Resin Transformer for 0.4~11 Kv Second VoltageHigh Efficiency Cast Resin Transformer for 0.4~11 Kv Second VoltageHigh Efficiency Cast Resin Transformer for 0.4~11 Kv Second Voltage

Cutting-Edge Equipment:


Precision Slitting Line

High Efficiency Cast Resin Transformer for 0.4~11 Kv Second Voltage

Efficient Shearing Line
High Efficiency Cast Resin Transformer for 0.4~11 Kv Second Voltage

State-of-the-art HEDRICH Vacuum Casting Tank
High Efficiency Cast Resin Transformer for 0.4~11 Kv Second Voltage

Advanced Curing Oven
High Efficiency Cast Resin Transformer for 0.4~11 Kv Second Voltage

Innovative Foil Winding
High Efficiency Cast Resin Transformer for 0.4~11 Kv Second Voltage

Comprehensive Testing Center
High Efficiency Cast Resin Transformer for 0.4~11 Kv Second Voltage
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now